CK10W-3/8.5
Specifications
| Specification | Conditions | Value |
|---|---|---|
| VRMS | AC | 2550 VAC |
| IMAX | For 8 x 20 μs Pulse | 10000 A |
| VR (L-N) | 3 kV | |
| VDC REF | At 1 mA | 4.3 kV |
| VRES | At Steep of 1 x 10 µs Pulse | 10.2 kV |
| VRES | For Lightning Impulse 8 x 20 µs | 8.8 kV |
| VRES | For Switching Impulse 30 x 60 µs | 7.5 kV |
| ISWC | For Current Impulse 4 x 10 µs | 100 kA |
| VBIL | For Lighning Impulse | 11.5 kV |
| VBIL | At Power Frequency, Wet 1 Minute | 8 kV |
| Str. Tor. | 50 N m | |
| Str. Can. | 147 N m | |
| Creepage | 215 mm | |
| A | 1.18 in. | |
| B | 1.18 in. | |
| C | 4.17 in. | |
| D | 6.53 in. | |
| E | 2.32 in. | |
| F | 4.64 in. |
Notes
- Meets IEC600 99-4.